KAL760

Provides a remote input to the fire system loop. The input is constantly monitored and its status communicated to the fire control panel. The input may be activated by closing or opening a potential free contact, depending on the module configuration. This module may be used to monitor any contact by showing its status through the fire control panel e.g. the monitoring of pressure equipment and closure fire break doors.

Specifications

Supply voltage:

22-38 VDC

Current consumption:

Quiescent @ 24 V:

110 µA

Quiescent @ 35 V:

135 µA

Alarm:

< 10 mA

Aux. 24 VDC quiescent:

200 µA

Aux. 24 VDC alarm:

< 50 mA

End-of-line resistor:

NA

Relay contact rating:

NA

Environmental:

Storage temperature:

-10°C to +50°C

Operating temperature:

-10°C to +70°C

Relative humidity (non-cond.):

95 %

Dimensions (l x w x h):

117 x 80 x 44 mm


Manufacturer: 
Price: 
96.00